Thursday 21 December 2006

Cranberry Foods - Derby
Frost protected 95m of stainless steel pipework by supping and installing our type VC constant wattage heating tape.

Monday 18 December 2006

Morris Lubricants Ltd - Shrewsbury
Supplied trace heating to maintain the external stainless steel pipework at +25°C.

Friday 15 December 2006

Reckitt Benckiser - Derby
ESH designed, supplied materials and labour to install and commission the trace heating for a vessel 3m dia x 3.6m tall to be maintained at 30°C.

Wednesday 13 December 2006

Eastry WWTW - Kent
Scope of work was to supply and install trace heating tape, lagging and cladding to provide frost protection to the following:

  • Inlet works
  • ABS pipework & valves, Safety Shower & Fernic Dosing Kiosk
  • ABS pipework & valve, PST 3
  • Ductile iron pipework, pumps and vales, Sandfilters
  • Stainless steel, ductile iron and ABS pipework, valve & filter

Friday 8 December 2006

Kingmill Hospital - Mansfield 
We supplied our type VC constant wattage heating tape to provide frost protection.
New Tesco Store - Livingston
Supplied tools and labour to install and commission the trace heating, lagging and cladding to frost protect the Adblue pipework.

Thursday 7 December 2006

Gist Ltd - Cumbernauld
Supplied materials and labour to install and commission the trace heating, lagging and cladding to the Adblue pipework within this large distribution centre.

Tuesday 5 December 2006

Eagle Centre - Derby




In this project we supplied and installed the Trace Heating for frost protection on the BCWS and LTHW services pipework within the basement area. The shopping centre ended up needing just under 2000m of heating cable in total.

Monday 4 December 2006

Nestle Purina - Suffolk
Within this pet food manufacturing plant we supplied and installed the trace heating tape to maintain 2", 3" and 4" stainless steel pipework at a temperature of 55 degrees C. With the pipework being both internal and external we needed to use VC30/1 and VC38/1 tapes to maintain the constant temperature throughout.
Newham STW - Truro
Within this Zone 1 Group IIB T3 Classification Hazardous Area, ESH supplied and installed trace heating to provide frost protection utilising ATEX approved self regulating tape in conjunction with ATEX approved air sensing thermostat units.